We use a few cookies

Essential cookies keep the library working. With your permission, we'd also like to use analytics to see what's useful and improve the experience. Read our Privacy Policy or Cookie Policy.

Skip to main content
Home/e-Resources/Chemical Engineering/Performance Evaluation of an Ejector Cooler Based on Mass and Energy Balance and Effectiveness at The ZK II Plant of PT XY
PeriodicalsChemical Engineering

Performance Evaluation of an Ejector Cooler Based on Mass and Energy Balance and Effectiveness at The ZK II Plant of PT XY

Checking your access to this record.

Abstract & Overview

Heat transfer in cooling systems is commonly enhanced by ejector coolers, which play a crucial role in chemical industry operations. This study evaluates the performance of an ejector cooler at the ZK II Plant of PT XY through effectiveness analysis, as well as mass and energy balance assessments. Operational data were obtained over the period of 15–21 October 2025 under steady-state plant conditions. The analysis is grounded in fundamental heat transfer relations and thermodynamic principles. The results indicate that the system effectiveness varies between 72.73% and 80.15%, reflecting relatively good thermal performance under actual operating conditions. In addition, the mass balance results confirm that the system remains in equilibrium between inlet and outlet streams. From the energy analysis, the heat transfer rate ranges from 4884.65 kJ/h to 9669.62 kJ/h, showing normal operational fluctuations within the plant. Meanwhile, the mass flow rate remains fairly stable, varying from 15.57 kg/h to 19.98 kg/h. Overall, the ejector cooler demonstrates satisfactory performance in real industrial operation. These effectiveness values may serve as a useful reference for similar cooling systems. The findings also suggest that maintaining stable operating conditions is essential to ensure consistent and efficient heat transfer performance.

Cite this record

Rosmawati Sipayung, Perdana Alfarez, Rifan Rizki (2026). Performance Evaluation of an Ejector Cooler Based on Mass and Energy Balance and Effectiveness at The ZK II Plant of PT XY. Research In Chemical Engineering (RiCE), 5(2). https://doi.org/10.30595/rice.v5i2.466

Copy in another style

Sipayung, R., Alfarez, P., & Rizki, R. (2026). Performance Evaluation of an Ejector Cooler Based on Mass and Energy Balance and Effectiveness at The ZK II Plant of PT XY. Research In Chemical Engineering (RiCE), 5(2). https://doi.org/10.30595/rice.v5i2.466
Author names are used as deposited, so check their order before you submit.

Metadata is harvested from open-access indexes and can be incomplete. Check a citation against the published version before relying on it — see our open access & attribution policy.