In recent years,flashover and condensation of generator isolated-phase bus occured frequently in some of the electric power enterprise,affecting safe and stable operation of power generation units and causing certain economic loss.Based on the accident example,the article has analyzed in isolated-phase bus from the cause of the incident,largely due to seal lax of the isolated-phase bus,imperfect protection system,the seasonal climate impact,decorate structure defects,protection device problems,isolated-phase bus to the influence of insulator.Introduce how to use the positive pressure device and the positive pressure device to prevent condensation in enclosed bus network.Make comparison and analysis of adsorptioning,condensing,polymer membrane of micro positive pressure equipment commonly used in China.