Abstract & Overview
Cantilever walls fixed at the base or slabs spanning a number of counterforts are the usually adopted structural systems for rectangular tanks of effluent treatment and water treatment plants. It is proposed to replace the counterfort-slab units by shell-cantilevers, which are known to be very efficient forms to resist loads. The orientation of such units will depend upon the governing load conditions, eg, convex inside when the water pressure from inside governs the design. Since these derive their strength from the shapes used, a strict adherence to geometry is required during construction, Circular segmental units are thus proposed to facilitate shape conforming construction. Material economy is quite evident. Wide availability of shuttering of cylindrical units with many construction agencies and the repetitive use of such formwork is expected to reduce construction costs. A finite element approach is needed for analysis and design of such components. Computer programs which can be run on small PCs are now widely available and these may be used even by small design offices. An illustrative example of a common effluent treatment plant, designed and constructed recently, has been presented. The reinforcement in the proposed shell-cantilever was mostly governed by the minimum steel provision stipulated by the code of practice.