Abstract & Overview
Individual generators in multi‐machine networks are represented by closed‐loop configurations of linear time‐ invariant modeling and nonlinear feedback, subject to modeling uncertainties and power disturbances, based on which control laws and implementation algorithms of static VAR compensators (SVC) are established to robustly stabilize individual generators by combining the gain‐ scheduling technique to the small‐gain theorem in the sense of finite‐gain 2 L ‐stability. The gain‐scheduling SVC manipulation approach can be implemented in multiple decentralized algorithms that involve only locally‐measured signals, and are robust against modeling uncertainties and power disturbances. The suggested SVC control laws can also accommodate the steady‐state performance specification in term of generator power angle, besides stabilization. As a special case of the suggested SVC control laws, examples are included to illustrate efficacy and simplicity of an averagely gain‐scheduling SVC control law.