Abstract & Overview
Digital twin (DT) technology is increasingly deployed in industrial power generation, including gas-piston plants supplying remote oil and gas fields in Kazakhstan. DTs improve efficiency and predictive maintenance but expand the attack surface by connecting sensors, PLCs, SCADA, IIoT gateways, cloud platforms, and AI modules into one control loop. This paper analyses cybersecurity threats specific to DT-based control of gas-piston power plants: a reference architecture for a 2 MW unit is defined, attack entry points are mapped, and a qualitative risk assessment is performed. Four attack scenarios — sensor spoofing, false data injection, denial of service, and AI model poisoning — are simulated on a synthetic 24-hour telemetry dataset. An eight-layer defence-in-depth framework aligned with IEC 62443, NIST SP 800-82, and NIST IR 8356 addresses classical ICS risks and DT-specific threats. Expert-based evaluation, partly corroborated by simulation, indicates a ≈65% reduction in aggregate cyber-risk score, providing a basis for securing intelligent control in distributed generation.