We use a few cookies

Essential cookies keep the library working. With your permission, we'd also like to use analytics to see what's useful and improve the experience. Read our Privacy Policy or Cookie Policy.

Skip to main content
Home/e-Resources/Robotics & Automation/Maintenance of Grounding Systems at Distribution Substations to Improve The Reliability of Electricity Distribution in The Work Area of PLN Customer Service Unit at Bima City
PeriodicalsRobotics & Automation

Maintenance of Grounding Systems at Distribution Substations to Improve The Reliability of Electricity Distribution in The Work Area of PLN Customer Service Unit at Bima City

Checking your access to this record.

Abstract & Overview

Distribution substations have an important role in maintaining the reliability of the electricity distribution system. In the working area of PLN ULP Bima City, disturbances often occur due to high grounding resistance values, declining equipment conditions, and external factors such as weather. These problems reduce system performance and increase the risk of electrical disturbances. The solution applied is measurable grounding maintenance using field inspection methods, technical interviews, and literature studies. The contribution of this activity is the preparation of an effective distribution substation maintenance procedure that complies with PLN standards. The methods used include predictive, preventive, and corrective maintenance, as well as replacement of components such as arresters, insulators, and A3CS cables. The results showed an initial resistance value of 18.22 Ω which dropped to 1.49 Ω after the installation of a new grounding system and integration with arresters. This decrease proves the effectiveness of the applied method in lowering the ground resistance and improving protection against lightning strikes. Maintenance also includes testing using a Hioki FT6031 Earth Tester with results that meet PLN standards. In conclusion, thorough grounding maintenance is able to improve the reliability of distribution substations and reduce potential interference, as well as support the reliability of electricity supply in the Bima City area in a sustainable manner

Cite this record

Aditama Muhamad Aswin Yusrih, I Ketut Wiryajati, Budiman Djul Fikry (2025). Maintenance of Grounding Systems at Distribution Substations to Improve The Reliability of Electricity Distribution in The Work Area of PLN Customer Service Unit at Bima City. JEITECH (JOURNAL OF ELECTRICAL ENGINEERING, INFORMATION TECHNOLOGY, CONTROL ENGINEERING, AND ROBOTIC). https://library.shubhaarti.com/content/f26bef07-c529-4a71-8943-d5ea897c93b8

Copy in another style

Yusrih, A. M. A., Wiryajati, I. K., & Fikry, B. D. (2025). Maintenance of Grounding Systems at Distribution Substations to Improve The Reliability of Electricity Distribution in The Work Area of PLN Customer Service Unit at Bima City. JEITECH (JOURNAL OF ELECTRICAL ENGINEERING, INFORMATION TECHNOLOGY, CONTROL ENGINEERING, AND ROBOTIC). https://library.shubhaarti.com/content/f26bef07-c529-4a71-8943-d5ea897c93b8
Author names are used as deposited, so check their order before you submit.

Metadata is harvested from open-access indexes and can be incomplete. Check a citation against the published version before relying on it — see our open access & attribution policy.