Home/e-Resources/Mechanical Engineering/Performance assessment of a novel auto-cascade heat pump using low-GWP refrigerant for obtaining high-temperature water
PeriodicalsMechanical Engineering

Performance assessment of a novel auto-cascade heat pump using low-GWP refrigerant for obtaining high-temperature water

Checking your access to this record.

Abstract & Overview

With the aim of developing a high-temperature heat pump with a large temperature lift, a novel auto-cascade heat pump using low global warming potential (GWP) refrigerant is proposed. Owing to the large exergy destruction between the refrigerant and heat sink with limited heat capacity, a cascade heating approach for obtaining high-temperature water is employed. A zeotropic refrigerant with temperature glide characteristics is selected as the working fluid. The modified heat exchange process reduces the temperature difference during heat transfer, thereby decreasing exergy destruction. A thermodynamic analysis model is established to assess the performance of the proposed auto-cascade heat pump cycle. The energy and exergy performances of the novel cycle are evaluated and compared with those of the basic cycle. Within the range of water outlet temperature considered here, the heating coefficient of performance and capacity increase by 51.1% and 50.6%, respectively. The proposed cycle decreases the mass flow rate of the refrigerant by 38.7% on average. For evaporating temperatures in the range 10–15 °C, the proposed cycle improves the heating coefficient of performance and capacity by 54.7% and 43.9% over the basic cycle. The exergy analysis indicates that excellent exergy performance mainly benefits from the reductions in irreversible destruction between refrigerant and water heat exchange. Overall, the thermodynamic analysis reveals the improvements achieved with the novel auto-cascade heat pump cycle.

Cite this record

Gang Yan, Yuqing Yang, Yinlong Li (2025). Performance assessment of a novel auto-cascade heat pump using low-GWP refrigerant for obtaining high-temperature water. International Journal of Fluid Engineering, 2(4), 044303. https://doi.org/10.1063/5.0238307

Copy in another style

Yan, G., Yang, Y., & Li, Y. (2025). Performance assessment of a novel auto-cascade heat pump using low-GWP refrigerant for obtaining high-temperature water. International Journal of Fluid Engineering, 2(4), 044303. https://doi.org/10.1063/5.0238307
Author names are used as deposited, so check their order before you submit.